HVAC Quote Request — 4000 Chamisa Dr

Jeff Brabant · Austin, TX 78730 · September 11, 2026 (v4, replaces everything earlier)

What we want

Where this document says "we", the owner is designing the acoustic side: the room's silencers, the wire port, the concrete walls. Your side is the equipment, the installation, and the numbers. Answer the questions in each section by email; there is no form.

Systems

System Where Nominal Equipment
System 1 — Garage Attic air handler in the attic above the garage; serves the first floor 4 ton Carrier Infinity 27VNA348 heat pump + FE5 air handler + Infinity control
System 2 — Master Attic air handler in the attic above the master bedroom; serves the second floor 5 ton Carrier Infinity 27VNA360 + FE5 + Infinity control
System 3 — Sound Room air handler in the garage attic, offset from the room 1 ton Mitsubishi PVA-AA12NL + PUZ-AK12NL
System 4 future second sound-room unit for a 20×20 room space in the chases and on the pad

Trane XV19 equivalents are an acceptable alternate for Systems 1 and 2, quoted separately. Tonnage is our estimate; your Manual J decides, and we want to see it. Use these system names on the quote, the labels, and the commissioning report.

Pricing

One price per system, one for the trench and chases, and, if you want the work, one for the pad and walls. Exact model numbers. Say what is excluded: electrical, permits, condensate, refrigerant for the actual lineset length. Commissioning measurements are part of the price. Valid 30 days.

Anything in this document you would price differently or leave out? Say what and why.

House systems (1 and 2)

The garage-attic air handler transmits sound into the framing today. It must not after replacement.

Do the air handlers stay where they are or move, and what total static do you expect on each?
Which isolation will you use, and what is its static deflection?

Sound room (System 3)

Goal: a room you cannot hear the HVAC in. It already has one silenced supply and one silenced return, each a 10×12 duct into the garage attic. You connect to those two ducts. Nothing else penetrates the room.

Lineset length from the pad to your air-handler location?
Fresh air: we think an ERV running about 30 CFM for two people is the minimum. Agree? Which unit, and how does it tie in?
What isolation will you use, and what is its deflection?
Which fan tap and ESP setting will you commission, and what CFM does that give?
Anything you would do differently?

Room openings

Goal: air enters and leaves the room at 100 fpm or less. No draft, no audible rush at the grilles.

Will you build the two boxes and grilles, or leave them to us? If you will, price them as a separate line.
Your proposed face size and grille type, with its free area, for 280 CFM.
Does the box add enough resistance to change the fan tap you would commission?

Pad and outdoor units

Goal: every condenser on one ground pad away from the house, behind concrete walls, and the yard stays quiet.

Site plan — pad location

Pad dimensions and stub-up locations you need. Mark them on the drawing.
Will you price the pad and walls, or should our concrete contractor?
Which isolation mounts?
Anything the walls or the fence do to airflow or noise that we should know?

Commissioning report

One page per system: weighed refrigerant charge for the actual lineset, measured airflow, measured static, fan and control settings, and photos of the isolation. For the sound room, the airflow and face-velocity numbers above.

Documents

Manufacturer data: Carrier 27VNA3 · Mitsubishi PVA-AA12NL / PUZ-AK12NL · Mitsubishi SVZ-AP12NL / SUZ-AA12NL. Full-lot site plan.